Viconics C1012 User Manual

Browse online or download User Manual for For Home Viconics C1012. Viconics C1012 User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
HOW TO ORDER
Thermostat C1010-02 C1011-02 ** C1012-02 C1013-02 **
Tri-state output in cooling mode
zzzz
Tri-state output reverses to heating mode
with change over sensor
zz
Auxiliary reheat 1 stage 1 stage
** these packages include the auto change over sensor.
C1012
Electronic Thermostat
APPLICATIONS
VAV and by-pass units control
with modulating tri-
state floating output
Single stage of auxiliary reheat
ADVANCED DESIGN AND PI CONTROL
Advanced PI control thermostats provides precise
temperature control and eliminates wasted energy caused
by the typical On / Off cycling in conventional thermostats.
Thus the room occupant is able to reduce the thermostat
setpoint to the lowest comfortable setting. The result is
energy savings ranging from 5% to 10%.
DIMENSIONS
50
90
80
70
60
F
114 mm
32 mm
( 71 mm )
( 71 mm )
2.8"
2.8"
4.5"
1.275"
5432176
( 83 mm )
3.275"
SECURITY SCREW
FROM BACK
WIRING
BASE
( 71 mm )
2.8"
SCREW TERMINALS
COVER TOP
COVER INSIDE
MODULATING TRI-STATE FLOATING OUTPUT
For use with tri-state floating actuator (CW/Off/CCW)
having a 1 to 2 minutes timing per 90° of rotation. This is
a true multi positions modulating output. It gives
performances which is equivalent to more expensive 0 to
10 Vdc type output.
SINGLE STAGE OF AUXILIARY REHEAT
To be used with On/Off 2 position 24 Vac devices like:
On/Off N.C. electric valves
Electric duct heater relays
Electric base board relays
See and study wiring diagrams carefully to wire reheat
devices using a separate power source.
COVERS
Factory standard scale is 10°C to 32°C for horizontal
mounting. °F & °C scales are available on special order
for horizontal or vertical mounting. The thermostat and the
terminals are an integral part of the cover. The cover
hooks onto the base for easy service and is locked in
place using a security screw.
SPECIFICATIONS
Operating
Conditions:
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
Sensor: Local 47 K NTC thermistor
Resolution: ± 0.1 °C ( ± 0.2 °F )
Control accuracy
(calibrated):
± 0.2 ° C ( ± 0.4 °F )
Ranges: 50 °F to 90 °F Standard
( 10 °C to 32 °C ) Optional
Outputs: Isolated Triac: 30 Vac at ½ A max.
Power: 24 VAC -15%, +10% 50/60 Hz; 2 VA
Specifications and equipment are subject to change without prior
notice.
Page view 0
1 2

Summary of Contents

Page 2 - C1012-02

Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 [email protected] LIT-C1012-E01C1012-02 W

Comments to this Manuals